4650 PEAK / 3600 RUNNING WATT DUAL FUEL • REMOTE ELECTRIC START • GENSTART BASE CONTROLLER
ACIDNI LLC | SEPTEMBER 2026 | REV 1.2
Connection Summary
GenStart Terminal
Connects To
Wire
START SIGNAL — SIGNAL
Inverter / transfer switch generator-start output, NO terminal
White, 22 AWG
START SIGNAL — COMMON
Inverter / transfer switch generator-start output, COM terminal
Black, 22 AWG
START/STOP 1
One wire of the WGen3600DFc push-button START/STOP switch (tapped in parallel)
Green, 18 AWG
START/STOP 2
The other wire of the same button (tapped in parallel)
Green, 18 AWG
BATTERY +
WGen3600DFc 12V starting battery, positive post or the + lead of its quick-connect plug — 3A inline fuse required
Red, 18 AWG
BATTERY −
WGen3600DFc 12V starting battery, negative post or the − lead of its quick-connect plug
Black, 18 AWG
AC SENSE L
Hot side of the 120V 5-20R duplex outlet on the generator panel
Orange, 18 AWG
AC SENSE N
Neutral side of the same outlet
White/Orange, 18 AWG
— (no GenStart terminal)
L5-30R or TT-30R → your inverter/charger AC input stays exactly as it is today
Existing cable
Settings — GenStart Web Page
Setting
Value for the WGen3600DFc
Why
Start Mode
Button
The WGen3600DFc starts from a lit panel push-button; its onboard controller handles choke, cranking and shutdown
Double-Press Gap
3 seconds
This start module needs two presses: the first wakes it (button lights), the second cranks — the same module behaviour as the Generac GP series
Press Length (Start)
1 second
Matches a firm press-and-release
Press Length (Stop)
1 second
A single press shuts the engine down
Start Confirm Time
15 seconds
AC power must appear within this window or the attempt counts as failed
Retries / Retry Delay
3 / 10 seconds
Automatic re-try; after 3 failures GenStart stops and reports a fault
⚠ CHECK YOUR PANEL FIRST: Stand at the generator and start it by hand with the button. If the first press lights the button and the second press cranks, leave Double-Press ON at 3 seconds as shown. If one press-and-hold starts it (the manual describes a 2-second hold), turn Double-Press OFF and set Press Length (Start) to 2.5 seconds. Then use GenStart's Test Run button and watch a full start, run and stop before you leave the system unattended. BATTERY SWITCH MUST STAY ON: The WGen3600DFc will not respond to the button, the key fob or GenStart while its battery switch is OFF. Leave it ON. The generator charges its own battery while running, but a small battery maintainer is cheap insurance for a remote site that only runs a few hours a week. CO SENSOR: If the generator shuts itself down for carbon monoxide, the manual requires a restart at the control panel. GenStart will retry 3 times, then report a fault. Never bypass the CO system, and keep the generator well away from buildings.
TAP IN PARALLEL: The two START/STOP wires splice alongside the existing push-button wires (posi-taps or solder and heat-shrink). Nothing is cut, so the panel button and the wireless key fob still work normally. NO OTHER CHANGES: Choke (automatic), ignition, fuel selector and the remote-start receiver stay factory — nothing to modify. WHY THE AC SENSE WIRES MATTER: They are how GenStart knows the engine actually started. Without them it cannot verify a start or retry a failed one. PROPANE: If you run on LPG, the tank valve must be left open for unattended starting to work. On gasoline, leave the fuel valve open and keep the tank topped up. SAFETY: Disconnect the generator battery before you begin wiring. Never work on the 120V outlet while the generator can start.