Predator 5000 Auto-Start Wiring

HARBOR FREIGHT SKU 71367 / 70143  •  GENSTART BASE CONTROLLER
ACIDNI LLC  |  JULY 2026  |  REV 2.0
YOUR INVERTER / TRANSFER SWITCH ANY 2-WIRE "GENERATOR START" DRY CONTACT GENERATOR START OUTPUT NO COM CONTACT CLOSED = start the generator CONTACT OPEN   = stop the generator WHITE BLACK GENSTART CONTROLLER BASE MODEL  •  WEATHERPROOF ENCLOSURE ALL CONNECTIONS ARE LABELED SCREW TERMINALS START SIGNAL IN SIGNAL COMMON GENERATOR START/STOP START/STOP 1 START/STOP 2 12V POWER IN BATTERY + BATTERY − GENERATOR RUNNING SENSE SENSE + SENSE − SETUP (in the GenStart app / web page) Start Mode: BUTTON  •  Double-Press: ON Press 1 sec → wait 3 sec → press 1 sec PREDATOR 5000 — SKU 71367 DUAL-FUEL INVERTER • CO SECURE • WIRELESS REMOTE ENGINE START / STOP BUTTON on the generator control panel its two wires TAP IN PARALLEL — DO NOT CUT ANYTHING GENERATOR 12V STARTING BATTERY + − install supplied 3A inline fuse on the + wire 5V USB ADAPTER + SENSE CABLE (SUPPLIED) + − plugs into any 120V outlet on the generator FACTORY WIRELESS REMOTE (2x FOB) KEEPS WORKING — NOTHING IS DISABLED LEAVE THE GENERATOR SET UP LIKE THIS • Engine / Battery switch — ON • Fuel selector — GASOLINE or PROPANE • Fuel / tank valve open, oil level good • Choke — automatic, nothing to wire • Battery maintainer recommended 2-wire WHAT HAPPENS, STEP BY STEP 1. Battery gets low — your inverter    closes its start contact 2. GenStart waits 3 seconds 3. Presses the START button once (1 sec) 4. Waits 3 seconds, presses again —    the engine cranks and starts 5. Confirms the generator is running    within 15 seconds — if not, it waits    10 sec and tries again (3 tries total) 6. Battery recharged — your inverter    opens the contact 7. GenStart presses the button once    more — the generator shuts down No one needs to touch the generator.

Connection Summary

GenStart TerminalConnects ToWire
START SIGNAL — SIGNALInverter / transfer switch generator-start output, NO terminalWhite, 22 AWG
START SIGNAL — COMMONInverter / transfer switch generator-start output, COM terminalBlack, 22 AWG
START/STOP 1One wire of the generator's Engine Start/Stop button (tapped in parallel)Green, 18 AWG
START/STOP 2The other wire of the same button (tapped in parallel)Green, 18 AWG
BATTERY +Generator 12V starting battery, positive post — 3A inline fuse requiredRed, 18 AWG
BATTERY −Generator 12V starting battery, negative postBlack, 18 AWG
SENSE +Red (+) lead of the supplied USB sense cable, plugged into the supplied USB adapter in any 120V outlet on the generatorUSB cable lead
SENSE −Black (−) lead of the same cableUSB cable lead

Start Signal — Three Ways

OptionHow it worksUse it when
1. Dry contact (wired)A 2-wire contact wired to START SIGNAL IN (SIGNAL and COMMON): your inverter's or transfer switch's generator-start output, or the normally-closed contact of a relay whose coil is powered by utility power. Closed = run the generator, open = stop it.The inverter or transfer switch is close enough to run two small wires to GenStart. Available now.
2. WirelessThe Wireless Dry Contact Bridge Kit: a signal-source board at the inverter reads its contact and sends it by radio to the GenStart board at the generator, which then starts and stops the generator exactly as shown on this page.The inverter is too far from the generator to run the wire. Available now (the kit replaces the controller).
3. Utility power lossA second supplied 5V USB adapter plugs into an outlet powered by the utility, not by the generator. Wire its USB cable's red (+) lead to START SIGNAL IN SIGNAL and its black (−) lead to BATTERY − (ground). Do not use COMMON for this: on GenStart, COMMON is a +5V output, not ground, and wired there GenStart cannot see the outage. In GenStart's web page, open Settings > Start signal and set Start signal type to Utility power loss (5 V adapter). When the adapter's 5V is gone for the Start delay after loss (default 10 seconds, 1–600), GenStart starts the generator. Once utility has been back for the Stop delay after return (default 300 seconds, 0–7200; 0 keeps it running until you stop it), GenStart stops it.Backup for utility power through a transfer switch, with no separate relay. Available now in firmware 3.15.8. A GenStart uses one start signal: the inverter dry contact (option 1) or utility power loss, not both.
UTILITY POWER LOSS: Anything that removes power from the utility adapter looks like an outage to GenStart: unplugging it, a tripped breaker on its circuit, or a damaged or disconnected cable will start the generator. Plug it into a dedicated utility outlet that stays on and that the generator does not feed (if the generator powers that outlet, GenStart never sees the outage end). Use the start delay after loss to ride through short blips.

Settings — GenStart Web Page

SettingValue for the Predator 5000Why
Start ModeButtonThis generator is started by a panel push-button, not a key or solenoid
Double-Press Gap3 secondsThe owner's manual says to press and release the Start/Stop switch twice
Press Length (Start)1 secondMatches a firm press-and-release
Press Length (Stop)1 secondA single press shuts the engine down
Start Confirm Time15 secondsThe 5V running-sense signal must appear within this window or the attempt counts as failed
Retries / Retry Delay3 / 10 secondsAutomatic re-try; after 3 failures GenStart stops and reports a fault
⚠ IMPORTANT — 12-HOUR STANDBY SHUTDOWN ON THIS MODEL: The Predator 71367's own controller stays in standby for 12 hours after the generator is shut off, then powers down completely to protect its battery. Once it has powered down, nothing can start it electrically — not GenStart, not the panel button, not the wireless fob. Someone has to flip the Engine/Battery switch OFF then ON by hand.
WHAT TO DO: Use GenStart's scheduled exercise run (a 30-second start, built into the app) at least once every 11 hours. Every successful start resets the 12-hour clock, so the generator stays ready indefinitely. If you need the generator to sit unused for days and still start on demand with nobody on site, this model is not the right choice — pick one without a standby timeout.
⚠ CO SECURE SAFETY LOCKOUT: If the generator ever shuts itself down for carbon monoxide, it disables all remote and electric starting until someone restarts it by hand. GenStart will make its 3 attempts and then report a fault. This is intentional — never bypass the CO system.
TAP IN PARALLEL: The two START/STOP wires splice alongside the existing button wires (posi-taps or solder and heat-shrink). Nothing is cut or removed, so the panel button and the wireless fob work exactly as they did before.
NO OTHER CHANGES: Choke, ignition, and fuel systems are factory — nothing to modify.
RUNNING SENSE — 5V USB, NO 120V INTO GENSTART: The supplied USB adapter plugs into a 120V outlet on the generator, and the supplied USB sense cable carries its 5V to SENSE + and −. It only has power while the generator is producing power, which is how GenStart knows the engine actually started; without it it cannot verify a start or retry a failed one. If your generator has its own USB port that is live only while the engine runs (check with a meter: 0V engine off, about 5V running), you can plug the USB sense cable into that instead and skip the adapter. Never wire 120V or 240V to any GenStart terminal.
SAFETY: Disconnect the generator battery before you begin wiring.
Start signal from your inverter
Start/stop button wires
12V battery power
Running sense (5V USB)
Negative / common